600 kWAI/HPC Liquid Cooling Flow
Estimate liquid-captured IT heat, residual air heat, and primary flow for an assumed water temperature differential.
Free · Manual inputs · No sign-in- 01Set the assumptions
4 inputs. Replace the examples with values for your scenario.
- 02Explore the result
Change an input to see how the estimate responds.
- 03Check the source
Use the formula and limitations below before acting.
Build your scenario
Enter illustrative values. Everything runs locally in your browser; this tool does not send your scenario to a server.
Total heat dissipated by the AI/HPC equipment.
Share of IT heat transferred to liquid; remaining heat stays air-side.
Estimated temperature change across liquid-cooled IT equipment.
Increment to the theoretical heat-balance flow rate.
Example values are for demonstration only, not detected site, circuit or contract settings.
Your results
Residual air-side heat
200 kWIdeal water flow
860.01 L/minFlow with planning margin
946.01 L/minLiquid kW = IT kW × captured fraction; flow L/min ≈ 60 × liquid kW ÷ (4.186 kJ/kg·°C × liquid ΔT °C), assuming water ≈ 1 kg/L.
Water-only thermal estimate; glycol changes heat capacity and flow. Does not cover pressure drop, heat exchanger approach, pump head, CDU redundancy, leaks or actual server thermal specifications.