Whip Calculator

Choose your whip and redundancy. See one clear total for the IT load the configuration supports.

Circuit configuration → Protected capacity

Default example: L6-30 · 208V · 30A · 80% · A/B redundant = 4.99 kW protected (PF 1.00).

Power & capacityCONCEPT VIEW
A FEEDB FEEDTwo feeds · one IT load
01Source02Distribution03IT load
A conceptual view of the electrical path. Verify the installed design.
01 / CONFIGURE

Circuit setup

L6-20 and L6-30 are single-phase 208V profiles. Three-phase options use line-to-line voltage and line current; verify the actual installed connector and PDU.

Use 80% as the default planning assumption. Only use 100% if the complete circuit, breaker, conductor and PDU path are approved for that continuous rating.

An A/B pair provides two physical feeds for one protected IT load. Each independent feed must support the full load after failover. This does not verify upstream independence.

One pair means one A whip and one B whip. Ten pairs means 20 physical whips, but only ten protected load allocations.

Redundancy presets: N, 2N; advanced N+1 and 2N+1. Calculations are browser-local, not live measurements or electrical certifications.

02 / RESULTS

Protected capacity

For an A/B pair, the two whips protect one IT load. We never add A and B together as usable protected capacity.

Total protected IT power4.99 kW

Across 1 A/B pair · 80% rating · PF 1

Estimated real power at the selected power factor; not a meter reading or verified contractual entitlement.

A feed4.99 kVAPer pair · available capacity
B feed4.99 kVAPer pair · backup capacity

A + B are NOT added. Each side must support the same protected load after failover.

Show electrical breakdown, physical capacity and engineering assumptions

Protected circuit rating

4.99 kVA

Nominal capacity at the selected rating, independent of PF.

Per-feed nameplate rating

6.24 kVA

Before the 80% rating factor.

Physical installed capacity

9.98 kVA

Includes redundant feeds; not additional protected IT capacity.

Redundancy reserve

4.99 kVA

Held for redundancy, not added to usable load.

How it is calculated

Volts across load × amps / 1000 = 6.24 kVA per feed.

At 80% rating: 4.99 kVA per feed; estimated real power at PF 1: 4.99 kW per feed.

Protected load = N required feeds or A/B pairs; redundant feeds are not counted twice.

With balanced dual-corded loads, normal A/B split is approximately 2.5 kVA per side across all pairs. Surviving side must support 4.99 kVA after a full-path failure.

One complete A or B system may be lost while the other N system supports the protected load.

  • Line-to-line voltage for 3-phase
  • Balanced load; steady-state power factor
  • User-selected 80% or 100% rating basis is not a code-based breaker sizing certification
  • Circuit rating uses kVA = volts × amperes × phase factor; estimated real kW applies the selected PF separately
  • Redundancy math assumes identical units at the entered electrical rating
  • 2N / 2N+1 assumes genuinely independent A and B paths and dual-path-capable load; the calculator does not verify independence

A 100% rating requires a fully verified 100%-rated electrical path; do not assume a 100%-rated breaker alone permits 100% continuous use. Planning estimate only. Confirm continuous-load limits, conductors, breakers, voltage, A/B independence, transfer behavior, upstream UPS/PDU capacity and redundancy design with the responsible electrical engineer.

ColoPreflightAI · Planning estimates only. No live monitoring, electrical certification or customer data uploads.