Power Usage Effectiveness (PUE)
1.4PUE & Energy Reuse
Calculate facility power usage effectiveness and modeled energy reuse effectiveness from consistent energy boundaries.
Free · Manual inputs · No sign-in- 01Set the assumptions
3 inputs. Replace the examples with values for your scenario.
- 02Explore the result
Change an input to see how the estimate responds.
- 03Check the source
Use the formula and limitations below before acting.
Build your scenario
Enter illustrative values. Everything runs locally in your browser; this tool does not send your scenario to a server.
IT electrical energy for the same measurement period.
All facility electrical energy in the same period and boundary.
Energy actually recovered for a qualifying external use, not merely dissipated heat.
Example values are for demonstration only, not detected site, circuit or contract settings.
Your results
Energy Reuse Effectiveness (ERE)
1.36Facility overhead energy
200,000 kWhModeled energy reuse / facility
2.86%PUE = total facility energy / IT energy; ERE = (total facility energy − qualifying reused energy) / IT energy.
Consistent reporting period, metering boundaries and eligibility are essential. ERE depends on qualifying reused energy under an applicable reporting method; this is not a certification or verified operational PUE.